Spefication
Modell | SUN-120K-G01P3-EU-AM8 | SUN-125K-G01P3-EU-AM8 | SUN-130K-G01P3-EU-AM8 | SUN-135K-G01P3-EU-AM8 | SUN-136K-G01P3-EU-AM8 |
Eingangsseite | |||||
Max. DC-Eingangsleistung (kW) | 180 | 187.5 | 195 | 202.5 | 204 |
Max. DC-Eingangsspannung (V) | 1100 | ||||
Anlauf DC-Eingangsspannung (V) | 250 | ||||
MPPT-Betriebsbereich (V) | 200-1000 | ||||
Max. DC-Eingangsstrom (A) | 40+40+40+40+40+40+40+40 | ||||
Max. Kurzschlussstrom (A) | 60+60+60+60+60+60+60+60 | ||||
Anzahl der MPP-Tracker | 8 | ||||
Anzahl der Strings pro MPP-Tracker | 4+4+4+4+4+4+4+4 | ||||
Ausgangsseite | |||||
Nennausgangsleistung (kW) | 120 | 125 | 130 | 135 | 136 |
Max. Wirkleistung (kW) | 132 | 135 | 135 | 135 | 136 |
Rated Output Voltage/Range (V) | 3L/N/PE 220/380V, 230/400V 0.85Un-1.1Un (this may vary with grid standards) | ||||
Nenn-Netzfrequenz (Hz) | 50 / 60 (fakultativ) | ||||
Betriebsphase | Dreiphasig | ||||
AC-Netz-Nennausgangsstrom (A) | 181.9/174 | 189.4/181.2 | 197/188.5 | 204.6/195.7 | 206.1/197.2 |
Max. AC-Ausgangsstrom (A) | 200/191.4 | 204.6/195.7 | 204.6/195.7 | 204.6/195.7 | 206.1/197.2 |
Ausgangsleistungsfaktor | >0.99 | ||||
Gesamte harmonische Stromverzerrung (THDi) | <3% | ||||
DC-Einspritzstrom (mA) | <0,5% | ||||
Netzfrequenzbereich | 45~55 or 55~65 (Optional) | ||||
Wirkungsgrad | |||||
Max. Wirkungsgrad | 98.8% | ||||
Euro-Effizienz | 98.3% | ||||
MPPT Wirkungsgrad | >99% | ||||
Schutz | |||||
DC Reverse-Polarity Protection | Ja | ||||
AC Short Circuit Protection | Ja | ||||
AC Output Overcurrent Protection | Ja | ||||
Output Overvoltage Protection | Ja | ||||
Insulation Resistance Protection | Ja | ||||
Ground Fault Monitoring | Ja | ||||
Anti-islanding Protection | Ja | ||||
Temperature Protection | Ja | ||||
Integrated DC Switch | Ja | ||||
Remote Software Upload | Ja | ||||
Remote Change of Operating Parameters | Ja | ||||
Surge Protection | DC Typ II / AC Typ II | ||||
Allgemeine Daten | |||||
Schrankgröße (BxHxT mm) | 1006×516×325.5 (Excluding Connectors and Brackets) | ||||
Gewicht (kg) | 103 | ||||
Topologie | Transformatorlos | ||||
Internal Consumption | <1W (Night) | ||||
Running Temperature | -25-65℃, >45℃ Derating | ||||
Ingress Protection | IP65 | ||||
Noise Emission (Typical) | ≤65 dB | ||||
Cooling Concept | Intelligente Kühlung | ||||
Permissible Altitude (m) | 4000 | ||||
Designed Lifetime | >20 Years | ||||
Grid Connection Standard | IEC 61727, IEC 62116, CEI 0-21, CEI 0-16, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105, VDE-AR-N 4110 | ||||
Operating Surroundings Humidity | 0-100% | ||||
Sicherheit EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||||
Eigenschaften | |||||
Anzeige | LCD 240 × 160 | ||||
Schnittstelle | RS485/RS232/Wifi/LAN |
Physical Diagram and Connection Method